WIKA operating instructions pressure transmitter model D-1x-7

2478159.05 12/2011 GB/D/F/E

GB

8. Faults

8. Faults

In the event of any faults, first check whether the pressure transmitter is mounted correctly, mechanically

and electrically.

Faults

Causes

Measures

No output signal

Cable break

Check the continuity

Deviating zero point signal

Overpressure safety exceeded

Observe the permissible overload limit

Deviating zero point signal

Too high/low working temperature

Observe the permissible temperatures

Constant output signal upon

change in pressure

Mechanical overload caused by

overpressure

Replace instrument; if it fails repeat-

edly, contact the manufacturer

Signal span too small

Mechanical overload caused by

overpressure

Replace instrument; if it fails repeat-

edly, contact the manufacturer

Signal span varies

EMC interference sources in the

environment; for example, frequency

converter

Shield instrument; cable shield;

remove source of interference

Signal span varies/inaccurate

Too high/low working temperature

Observe the permissible temperatures

Signal span drops / too small

Signal span drops / too small

Contact manufacturer and replace

instrument

If complaint is unjustified, we will charge you the complaint processing fees.

CAUTION!

If deficiencies cannot be eliminated by means of the measures listed above, shut down the

instrument immediately, and ensure that pressure and/or signal are no longer present, and

secure the instrument from being put back into operation inadvertently. In this case, contact

the manufacturer. If a return is needed, please follow the instructions given in chapter "9.2

Return".