Fig. 11: Measurement setup, flow measurement in vapours
1
Condensate vessels
2
Orifice or impact pressure probe
3
Blocking valves
4
DPT10
5
Precipitator
6
Drain valves
7
3
-fold valve block
à Mount DPT10 below the measurement loop so that the effective
pressure lines are always filled with liquid and gas bubbles can
bubble up to the process line
à For measurements in products with solid content such as e.g. dirty
liquids, the installation of separators and drain valves is
recommended to enable collection and removal of debris and
sediment.
à Fill the effective pressure lines to the height of the condensate
vessels before setup