4 density and interface measurement, 5 differential pressure measurement, 5 differential pressure measurement – WIKA DPT-10 User Manual

Page 66

Advertising
background image

Now:

Valve 3, 6 and 7 are closed

Valves 2, 4, A and B are open.

Then carry out adjustment, see chapter "Set parameters".

8

.4 Density and interface measurement

For density and interface measurements, DPT10 with bilateral isolating
diaphragm CSB is used.

DPT

10 in this version is immediately ready for operation.

8

.5 Differential pressure measurement

For differential pressure measurements, DPT10 without isolating
diaphragm or with bilateral isolating diaphragm CSB is used.

DPT

10 with bilateral isolating diaphragm CSB is immediately ready for

operation.

Before adjusting DPT10 without isolating diaphragm, the effective
pressure lines must be cleaned and the instrument filled with medium.

+

I

II

+

6

7

3

2

4

A

B

Fig. 49: Preferred installation for gases

I

DPT10

II

3

-fold valve block

2

, 4 Inlet valves

3

Breather valve

6

, 7 Vent valves on DPT10

A, B Blocking valves

Instructions

Installation for gases

66

Differential pressure transmitter DPT10 - metal measuring diaphragm • Profibus PA

8 Set up

37245

-EN

-100120

Advertising