Fig. 46: Preferred installation for open vessels
I
DPT10
II
Precipitator
1
Drain valve
6
.7 Vent valves on DPT10
A
Blocking valve
Proceed as follows:
1
Fill the vessel to just over the lower tap.
2
Fill measuring system with medium.
Open valve A: Medium flows in.
3
Vent instrument
Briefly open valve 6, then close it: Fill the measuring instrument
completely with the medium and remove air.
4
Set measurement loop to operation
Now:
Valve A open and valve 6 closed
Then carry out adjustment, see below.
Installation for open
vessels
Prepare the adjustment
Differential pressure transmitter DPT10 - metal measuring diaphragm • Profibus PA
63
8 Set up
37245
-
EN