WIKA IUT-11 User Manual

Page 38

Advertising
background image

Universal IS Pressure Transmitter UniTrans

Operation of Devices without Displays

22

669

39

.0

5 D

/G

B

06

/2

00

6

Subject to change due to technical modifications.

© Copyright WIKA Alexander Wiegand GmbH & Co. KG / Germany

WIKA Alexander Wiegand GmbH & Co. KG · Alexander-Wiegand-Str. · 63911 Klingenberg · (09372) 132 - 710 · Fax - 706 · E-mail: [email protected] · www.wika.de

113

8.3

Calibration with Pressure

8.3.1 Zero Point Calibration

8.3.2 Span Calibration

Calibration of the measurement range (span).

Make sure that the pressure to be used as the zero point (P 0 %), is
present at the transmitterer diaphragm before calibration.

Make sure that the pressure to be used as the span end-point (P 100 %) is
present at the transmitter diaphragm. The measuring range between zero
and end value of span is saved as span.

A change in the zero point has no effect on the calibrated span.
However, if the span end-point is higher than the peak value of the sen-
sor’s nominal pressure range, then span end-point is fixed at this peak val-
ue and the span is reduced accordingly.
A change in the span setting has no effect on the zero point. The zero point
and span end-point must fall within the sensor’s nominal pressure range.
A mounting correction must not be carried out when making an adjustment
with pressure (wet adjustment). Otherwise, the mounting correction must
be carried out before saving the zero point and the end value of span.

meas

Zero point calibration

Calibration Value

Confirm

Function

(2 sec.)

(2 sec.)

(2 sec.)

024-DS-GB

meas

Calibration of span

Calibration Value

Confirm

Function

(2 sec.)

(2 sec.)

(2 sec.)

025-DS-GB

Advertising
This manual is related to the following products: