Universal IS Pressure Transmitter UniTrans

Transmitter Operation with HART®-functionality

Subject to change due to technical modifications.

© Copyright WIKA Alexander Wiegand GmbH & Co. KG / Germany

WIKA Alexander Wiegand GmbH & Co. KG · Alexander-Wiegand-Str. · 63911 Klingenberg · (09372) 132 - 710 · Fax - 706 · E-mail: [email protected] · www.wika.de

138

10.2.5 Submenu 'Parameter' - Output

Damping:

An average value of the pressure values applied to the sensor is calculated over the
predefined integration time. The following integration times can be set:
• 0, 1, 5, 20 and 40 s.

Output inversion:

The output signal can be inverted or not inverted.
• inverted

20 ... 4 mA

• not inverted 4 ... 20 mA

Alarm/Error:

Here the current value is displayed, which is set for an error message:
• 21.0 mA (upscale) or
• 36 mA (downscale).

Output current limits:

Here the range of output current is set.
• 3.8 ... 20.5 mA

When the applied pressure rises beyond the nominal range the current value ends
at the set limit value.

• 4 ... 20 mA

When the applied pressure rises beyond the nominal range and the alarm goes off
a reset must be carried out, or the power supply must be cut
(see also chapter 10.2.7).