FMI CL1 User Manual

Page 2

Advertising
background image

Supply Voltage: 0-90 VDC (Supplied by C100A Controller)
CL Supply: 1/4” NPT female

CL Recirculation return: 1/4” NPT female

CL High Pressure outlet: 1/4” NPT female

Output Volume: CL1: 6.5 GPH max.

CL2: 15 GPH max.

Output Pressure: 125 psi max.
Environment: Humidity: 100% RH non-condensing

Temp: non-freezing to 104°F

Enclosure: Fiberglass
Dimensions: 15 1/2” x 13 3/8” x 6 3/4”
Weight: 18.6 lbs. (8.4 kg.)

CL SPECIFICATIONS

CL INSTALLATION & SETUP

The Chloritrol

®

CL prefers to “lift fluid” and therefore

should be located a minimum of 12 inches above supply

vessel. It should also be mounted in an accessible

location where the cover can be opened freely.

Diagram 5

illustrates the recommended mounting location, as well as

a typical system configuration.


MOUNTING

Securely fasten the CL to a wall location with its right side

convenient to the hypochlorite supply vessel. There are 4

mounting holes (5/16” dia) on each side of the CL

enclosure. Utilize at least 2 holes on each side for most

secure mounting.

Diagram 1 (left) shows the mounting

hole locations.

Diagram 2

(Right Side)

Diagram 3

(Left Side)

ELECTRICAL

On the upper left side of the Chloritrol® CL

enclosure is a 7/8” conduit opening for the electrical

supply (0-90 VDC source from the C100A or FMI

approved customer supplied voltage controller).

Note: See page 5 “Wiring Procedure” for

additional information regarding wire sizing.

1.

With the power off, and the manual speed dial

turned fully counterclockwise to the “0” position,

connect the C100A to the 120 VAC power

source.


2.

Connect the C100A Variable Speed DC Controller

to the Chloritrol

®

using 3 conductor cable.


3.

If electronic speed control is being used, connect

the 4-20 mA source (typically a sensor or

analyzer), to the 4-20 mA input of the C100A.

Diagram 4

Terminal Wiring

IMPORTANT NOTE: There are two (2) vent holes located at the top front of the enclosure (under the upper lip of the

enclosure cover). Do not close, seal, or obstruct these vent openings. They are designed to prevent hazardous gases from

building up in the enclosure over time.

See Diagram 1.

Vent

Vent

CL SUPPLY INPUT

ELECTRICAL

CL RETURN

TO SUPPLY

CL DISPENSE

IN-CL-14

3/11/14 HW

Page 2 of 10

Diagram 1

Mounting Holes