7. Set the Ki parameters for both channels to a

value between 50 and 500 in order to bring each

CHANNEL to its exact set point. Be sure to cycle

the GUN between READY and RUN to send the

Ki values to the Channel Modules.

8. Normally, Kd may remain at zero. Set Kd to a

value between 50 and 500 if there appears to be

a delay in the response.