L.B. White COMBO-MCS User Manual

Page 12

Advertising
background image

■

Press the center soft key EDIT.

■

Press the up/down keys to enable (ENA) or disabled (dSA)

Zone 1 Temperature Sensor 1. See Fig. 29. Make the
same selections for sensors 2 through 4 for Zone 1.

FIG. 29

■

Once all have been selected for Zone 1, Temperature
Sensor 1 through 4, , press the right soft key NEXT to
access Zone 2, Temperature Sensor 1. Enable the sensor
using the up/down keys. When completed, press the left
soft key DONE.

■

To continue set-up, press right soft key NEXT. The following
screen is displayed.

C

CALIBRATING TEMPERATURE SENSORS

This selection allows correlation between the room
controller’s sensors and the SmartBox

™

sensors.

FIG. 30

■

Press the center soft key EDIT. The following screen is

displayed.

FIG. 31

-- Before making any adjustments, you must allow the

temperature between the room controller sensors
and the SmartBox

™

sensors to stabilize.

-- Once temperatures have stabilized, use the up/down

keys to enter room temperature sensor offset.

■

Press the right soft key NEXT to set temperature offset for

Zone 1, Temperature Sensors 1 through 4. Complete
the same process for Zone 2, Temperature Sensor 1.
Use the up/down keys accordingly.

-- Example: If the room controller reads 70 F and the

SmartBox

™

reads 69 F, set the offset temperature 1F

by pressing the up key.

■

Press the leftsoft key DONE, then press NEXT. The

following screen is displayed

FIG. 32

■

Press the center soft key EDIT to view the heat load

percent in Zone 1. See Fig. 33. To view Zone 2, press right
center soft key NEXT

FIG. 33

■

Press the up/down keys and center soft key

simultaneously to exit the set-up mode and to return you
back to the Home Screen. Now determine your
temperature curve.

12