Table 5 — Supply Air Sensor

Temperature/Resistance Values

TEMPERATURE (F)

RESISTANCE (ohms)

–58

200,250

–40

100,680

–22

53,010

–4

29,091

14

16,590

32

9,795

50

5,970

68

3,747

77

3,000

86

2,416

104

1,597

122

1,080

140

746

158

525

176

376

185

321

194

274

212

203

230

153

248

116

257

102

266

89

284

70

302

55

FOR OCCUPANCY CONTROL
REPLACE JUMPER WITH
FIELD-SUPPLIED TIME CLOCK

LEGEND

DCV— Demand Controlled Ventilation
IAQ — Indoor Air Quality
LA — Low Ambient Lockout Device
OAT — Outdoor-Air Temperature
POT — Potentiometer
RAT — Return-Air Temperature

Potentiometer Defaults Settings:
Power Exhaust

Middle

Minimum Pos.

Fully Closed

DCV Max.

Middle

DCV Set

Middle

Enthalpy

C Setting

NOTES:

1. 620 ohm, 1 watt 5% resistor should be removed only when using differential

enthalpy or dry bulb.

2. If a separate field-supplied 24 v transformer is used for the IAQ sensor power

supply, it cannot have the secondary of the transformer grounded.

3. For field-installed remote minimum position POT, remove black wire jumper

between P and P1 and set control minimum position POT. to the minimum
position.

Fig. 20 — EconoMi$er IV Wiring

0

5

10

15

20

25

30

0.13 0.20 0.22 0.25 0.30 0.35 0.40 0.45 0.50

STATIC PRESSURE (in. wg)

FLOW IN CUBIC FEET

PER MINUTE (cfm)

0

500

1000

1500

2000

2500

0.05

0.15

0.25

STATIC PRESSURE (in. wg)

FLOW IN CUBIC FEET

PER MINUTE (cfm)

Fig. 21 — Barometric Flow Capacity

Fig. 22 — Outdoor Air Damper Leakage