V. STEP 5 — MAKE ELECTRICAL CONNECTIONS

A. Field Power Supply
All units except 208/230-v units are factory wired for the
voltage shown on the nameplate. If the 208/230-v unit will be
connected to a 208-v power supply, the transformer must be
rewired by moving the black wire from the 230-v

1

/

4

-in. male

spade terminal on the transformer and connecting it to the
200-v

1

/

4

-in. male spade terminal on the transformer.

Refer to the unit label diagram for additional information.
Pigtails are provided for field wire connections. Use factory-
supplied splices or a UL (Underwriters’ Laboratories)
approved copper/aluminum connector.

When installing units, provide a disconnect per NEC.

All field wiring must comply with the NEC and local require-
ments. In Canada, electrical connections must be in accor-
dance with CSA (Canadian Standards Association) C22.1
Canadian Electrical Code Part One.

Install field wiring as follows:

1. Install conduit through the side panel openings. For

units without electric heat, install conduit between
the disconnect and control box.

2. Install power lines to terminal connections as shown

in Fig. 6.

3. For units with electric heat, refer to Table 2 and

Accessory Installation Instructions.

NOTE: During operation, voltage to compressor terminals
must be within the range indicated on the unit nameplate
(see Tables 3A-3D). On 3-phase units, voltages between
phases must be balanced within 2%, and the current within
10%. Use the formula shown in Tables 3A-3D, Note 2 on
page 9 to determine the percentage of voltage imbalance.
Operation on improper line voltage or excessive phase imbal-
ance constitutes abuse and may cause damage to electrical
components. (Such operation would invalidate any applica-
ble Bryant warranty.)

Table 2 — Electric Heating Capacities

*Two heater packages required to provide kW indicated.
NOTES:
1. The rated heater voltage is 240 and 480 v. If power distribution voltage varies

from rated heater voltage, heater kW will vary accordingly.

2. To determine heater kW at voltages other than those shown in table, use the

following formula:
Heater kW

new

= Heater kW

rated x

(unit power distribution voltage/rated heater

voltage)

2

As an example:

For a 16 kW heater rated at 240 v with a power distribution voltage of 215 v
kW

new

= 16 kW (215/240)

2

kW

new

= 12.8 kW (rating at 215 v)

WARNING: Unit cabinet must have an uninter-

rupted, unbroken electrical ground to minimize the
possibility of personal injury if an electrical fault
should occur. This ground may consist of electrical wire
connected to unit ground lug in control compartment,
or conduit approved for electrical ground when
installed in accordance with NEC (National Electrical
Code), ANSI/NFPA (American National Standards
Institute/National Fire Protection Association), latest
edition, and local electrical codes. Failure to follow this
warning could result in the installer being liable for
personal injury of others.

UNIT
549B

UNIT VOLTAGE

(60 Hz)

ACCESSORY

kW

ELECTRIC HEATER PART NUMBER

CRHEATER---A00

SINGLE POINT BOX PACKAGE NO.

CRSINGLE---A00

090

208/230/240

(3 phase)

7.8/ 9.6/10.4

12.0/14.7/16.0
18.6/22.8/24.8
24.0/29.4/32.0
31.8/39.0/42.4*

017
010
011
012
012 and 017

007
007
009
009
013

460/480

(3 phase)

12.8/13.9
15.2/16.5
25.6/27.8
30.4/33.0
38.4/41.7*

016
013
014
015
014 and 016

006
006
008
008

102

208/230/240

(3 phase)

7.8/ 9.6/10.4

12.0/14.7/16.0
18.6/22.8/24.8
24.0/29.4/32.0
31.8/39.0/42.4*

117
110
111
112
112, 117

012
012
015
015
017

460/480

(3 phase)

12.8/13.9
15.2/16.5
25.6/27.8
30.4/33.0
38.4/41.7*

116
113
114
115
114,116

011
011
014
014
016

120

208/230/240

(3 phase)

7.8/ 9.6/10.4

12.0/14.7/16.0
24.0/29.4/32.0
31.8/39.0/42.4*
37.6/46.2/50.0*

017
010
012
012 and 017
010 and 012

012
012
015
017
017

460/480

(3 phase)

15.2/16.5
25.6/27.8
30.4/33.0
38.4/41.7*
46.2/50.0*

013
014
015
014 and 016
013 and 015

011
014
014
016
016

LEGEND

C

Contactor

COMP — Compressor
IFC

Indoor Fan Contactor

NEC

National Electrical Code

Field Wiring
Factory Wiring
Splice Connection
(Factory-Supplied)

208/230-3-60

460-3-60

Fig. 6 — Power Wiring Connections