Bryant 549B User Manual

Page 19

Advertising
background image

19

Table 7 — CO

2

Sensor Standard Settings

LEGEND

ppm — Parts Per Million

Dehumidification of Fresh Air with DCV Control

Information from ASHRAE indicates that the largest humid-
ity load on any zone is the fresh air introduced. For some
applications, an energy recovery unit is added to reduce the
moisture content of the fresh air being brought into the
building when the enthalpy is high. In most cases, the nor-
mal heating and cooling processes are more than adequate to
remove the humidity loads for most commercial applications.

If normal rooftop heating and cooling operation is not ade-
quate for the outdoor humidity level, an energy recovery unit
and/or a dehumidification option should be considered.

VII. STEP 7 — ADJUST INDOOR-FAN SPEED

Adjust the indoor-fan speed to meet jobsite requirements.

For units with electric heat, required minimum cfm is
2250 for 549B090 and 102 and 3000 for 549B120 with the
following exceptions:

Table 8 shows indoor-fan motor data. Table 9 shows fan rpm
at motor pulley settings for standard and alternate motors.
Tables 10 and 11 show FIOP/accessory static pressure. Refer
to Tables 12-23 to determine fan speed settings. Fan motor
pulleys are factory set for speed shown in Table 1.

To change fan speeds:

1. Shut off the unit power supply and tag disconnect.

2. Loosen belt by loosening fan motor mounting nuts

See Fig. 31 and 32.

3. Loosen the movable pulley flange setscrew (see

Fig. 33).

4. Screw the movable flange toward the fixed flange to

increase speed and away from the fixed flange to
decrease speed. Increasing fan speed increases the
load on the motor. Do not exceed the maximum speed
specified in Table 1.

5. Set the movable flange at the nearest keyway of the

pulley hub and tighten the setscrew. (See Table 1 for
speed change for each full turn of the pulley flange.)

To align fan and motor pulleys:

1. Loosen the fan pulley setscrews.

2. Slide the fan pulley along the fan shaft.

3. Make angular alignment by loosening the motor from

the mounting plate.

SETTING

EQUIPMENT

OUTPUT

VENTILATION

RATE

(cfm/Person)

ANALOG

OUTPUT

CO

2

CONTROL RANGE

(ppm)

OPTIONAL

RELAY SETPOINT

(ppm)

RELAY

HYSTERESIS

(ppm)

1

Interface w/Standard
Building Control System

Proportional

Any

0-10V

4-20 mA

0-2000

1000

50

2

Proportional

Any

2-10V

7-20 mA

0-2000

1000

50

3

Exponential

Any

0-10V

4-20 mA

0-2000

1100

50

4

Economizer

Proportional

15

0-10V

4-20 mA

0-1100

1100

50

5

Proportional

20

0-10V

4-20 mA

0- 900

900

50

6

Exponential

15

0-10V

4-20 mA

0-1100

1100

50

7

Exponential

20

0-10V

4-20 mA

0- 900

900

50

8

Health & Safety

Proportional

0-10V

4-20 mA

0-9999

5000

500

9

Parking/Air Intakes/
Loading Docks

Proportional

0-10V

4-20 mA

0-2000

700

50

UNIT
549B

UNIT

VOLTAGE

HEATER

kW

UNIT

CONFIG-

URATION

REQUIRED

MINIMUM

CFM

120

208/230

42.4

Horizontal

3200

208/230

50.0

Horizontal

3200

460

50.0

Horizontal

or

Vertical

3200