Fig. 1 — roof curb details – Bryant 549B User Manual

Page 2

Advertising
background image

2

A minimum clearance to combustibles is not required around
ductwork on vertical discharge units. On horizontal dis-
charge units, a minimum clearance of 1 in. is required for the

first 12 in. of ductwork. Cabinet return-air static pressure (a
negative condition) shall not exceed 0.30 in. wg with econo-
mizer or 0.45 in. wg without economizer.

CONNECTOR PKG.

ACCY.

B

C

D ALT DRAIN HOLE

GAS

POWER

CONTROL

ACCESSORY POWER

CRBTMPWR001A01

2

′-8

7

/

16

[827]

1

′-10

15

/

16

[583]

1

3

/

4

[44.5]

3

/

4

″ [19] NPT

3

/

4

″ [19] NPT

1

/

2

″ NPT

[12.7]

1

/

2

″ NPT

[12.7]

CRBTMPWR002A01

1

1

/

4

″ [31.7]

CRBTMPWR003A01

1

/

2

″ [12.7] NPT

3

/

4

″ [19] NPT

1

/

2

″ NPT

[12.7]

CRBTMPWR004A01

3

/

4

″ [19] NPT

1

1

/

4

″ [31.7]

NOTES:

1. Roof curb accessory is shipped disassembled.
2. Insulated panels: 1-in. thick polyurethane foam, 1

3

/

4

lb

density.

3. Dimensions in [

] are in millimeters.

4. Roof curb: 16-gage steel.
5. Attach ductwork to curb (flanges of duct rest on curb).
6. Service clearance 4 ft on each side.

7.

Direction of airflow.

8. Connector packages CRBTMPWR001A01 and 2A01

are for thru-the-curb gas type. Packages
CRBTMPWR003A01 and 4A01 are for thru-the-bottom
type gas connections.

Fig. 1 — Roof Curb Details