To adjust belt tension:

1. Loosen the fan motor mounting plate nuts.

2. Size 090 and 102 — Slide the motor mounting plate

away from the fan scroll for proper belt tension (

5

/

8

-in.

deflection with 8 to 10 lb of force) and tighten the
mounting nuts (see Fig. 31).

Size 120 — Slide the motor mounting plate down-
ward to tighten belt tension (

5

/

8

-in. deflection with 5

to 10 lb of force). Secure the motor mounting plate
nuts. See Fig. 32.

3. Adjust the bolt and nut on the mounting plate to

secure the motor in a fixed position.

Table 8 — Indoor-Fan Motor Performance

LEGEND

Bhp — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horsepower range of the motors

can be utilized with confidence. Using fan motors up to the horsepower ratings shown in this table will not
result in nuisance tripping or premature motor failure. Unit warranty will not be affected.

UNIT
549B

INDOOR-FAN

MOTOR

UNIT

VOLTAGE

MAXIMUM ACCEPTABLE

CONTINUOUS BHP*

MAXIMUM ACCEPTABLE

OPERATING WATTS

MAXIMUM

AMP DRAW

090 and

102

Standard

208/230

2.90

2615

8.6

460

3.9

High Static

208/230

4.20

3313

11.7

460

5.5

120

Standard

208/230

3.70

3313

11.7

460

5.5

High Static

208/230

5.25

4400

17.3

460

8.5

Fig. 32 — Typical Belt-Drive Motor

Mounting for Size 120

Fig. 33 — Indoor-Fan Pulley Adjustment

Fig. 31 — Typical Belt-Drive Motor

Mounting for Sizes 090 and 102

MOTOR MOUNTING

PLATE NUTS