Bryant 549B User Manual

Page 37

Advertising
background image

37

C. Condensate Drain

Check and clean each year at the start of the cooling season.
In winter, protect against freeze-up.

D. Filters

Clean or replace at the start of each heating and cooling
season, or more often if operating conditions require it.
Replacement filters must be the same dimensions as original
filters.

E. Outdoor-Air Inlet Screen

Clean the screen with stream or hot water and a mild deter-
gent. Do not use disposable filters in place of screens.

II. LUBRICATION

A. Compressors

Each compressor is charged with the correct amount of oil at
the factory.

B. Fan-Motor Bearings

Fan-motor bearings are permanently lubricated. No lubrica-
tion of outdoor or indoor-fan motors is required.

III. OUTDOOR-FAN ADJUSTMENT (Fig. 37)

1. Shut off the unit power supply, and install lockout tag

on disconnect.

2. Remove the outdoor-fan assembly (grille, motor,

motor cover, and fan) and loosen the fan hub
setscrews.

3. Adjust the fan height as shown in Fig. 37.

4. Tighten the setscrews and replace the outdoor-fan

assembly.

IV. BLOWER BELT ADJUSTMENT

Inspect the blower belt for wear, proper belt tension, and
pulley alignment as conditions require or at the beginning of
each heating and air conditioning season.

Refer to Step 7 — Adjust Indoor-Fan Speed on page 19 for
adjustment and alignment procedure.

V. ECONOMI$ER IV ADJUSTMENT

Refer to Optional EconoMi$er IV section on page 12.

VI. HIGH-PRESSURE SWITCH

Located on the compressor hot gas line is a high-pressure
switch with a Schrader core depressor. This switch opens at
428 psig and closes at 320 psig. No adjustment is necessary.
Refer to Table 1.

VII. LOSS OF CHARGE SWITCH

Located on the outdoor liquid line is a low-pressure switch
which functions as a loss-of-charge switch. This switch con-
tains a Schrader core depressor. This switch opens at 7 psig
and closes at 22 psig. No adjustment is necessary. Refer to
Table 1.

VIII. FREEZESTAT

Located on the “hair pin” end of the indoor coil is a bimetal
temperature sensing switch. This switch protects the indoor
coil from freeze-up due to lack of airflow. The switch opens at
30 F and closes at 45 F. No adjustment is necessary. Refer to
Table 1.

IX. REFRIGERANT CHARGE

The amount of refrigerant charge is listed on the unit name-
plate (also refer to Table 1).

Unit panels must be in place when the unit is operating dur-
ing charging procedure. The unit must operate for a mini-
mum of 10 minutes before checking or adjusting the charge.

A. No Charge

Use standard evacuating techniques. After evacuating the
system to 500 microns, weigh in the specified amount of
refrigerant (refer to Table 1).

B. Low Charge Cooling

Use Cooling Charging Charts, Fig. 38-40. Vary refrigerant
until the conditions of the appropriate chart are met. Note
that charging charts are different from the type normally
used. The charts are based on charging the units to the cor-
rect superheat for the various operating conditions. An accu-
rate pressure gage and temperature sensing device are
required. Connect the pressure gage to the service port on
the suction line. Mount the temperature sensing device on
the suction line and insulate it so that outdoor ambient tem-
perature does not affect the reading. Indoor-air cfm must be
within the normal operating range of the unit.

Fig. 37 — Outdoor Fan Adjustment

UNIT VOLTAGE

‘‘A’’ in.

208/230 V

2.75

460 V

3.50

Fig. 36 — Separating Coil Sections

Advertising