A. Positioning

Maintain clearance around and above the unit to provide
proper airflow and service access. See Fig. 5.

Position the unit on the roof curb so that the following clear-
ances are maintained:

1

/

4

-in. clearance between the roof curb

and the base rails on each side and the duct side of unit;
3

5

/

16

-in. clearance between the roof curb and condenser side

of unit (see Fig. 1, section C-C).

Do not install the unit indoors. Do not locate the unit air inlet
near exhaust vents or other sources of contaminated air.

Although the unit is weatherproof, guard against water from
higher level runoff and overhangs.

After the unit is in position, remove the polyethylene ship-
ping wrapper and rigging skid.

Table 1 — Physical Data

LEGEND

BASE UNIT 549B

090

102

120

NOMINAL CAPACITY (tons)

7

1

/

2

8

1

/

2

10

OPERATING WEIGHT (lb)

Unit

870

1000

1000

EconoMi$er IV

75

75

75

Roof Curb

223

223

223

COMPRESSOR

Scroll

Quantity

2

2

2

Oil (oz) (each compr)

57

70

57

REFRIGERANT TYPE

R-22

Operating Charge (lb)

Circuit 1

9.5

11.0

10.7

Circuit 2

9.5

11.0

10.8

OUTDOOR FAN

Propeller

Quantity...Diameter (in.)

2...22

2...22

2...22

Nominal Cfm

6500

6500

6500

Motor Hp...Rpm

1

/

4

...1100

1

/

4

...1100

1

/

4

...1100

OUTDOOR COIL

Enhanced Copper Tubes, Aluminum Fins, Fixed Orifice Metering Device

Rows...Fins/in.

2...17

2...17

2...17

Total Face Area (sq ft)

20.5

25.1

25.1

INDOOR FAN

Centrifugal Type

Quantity...Size (in.)

Standard

1...15 x 15

1...15 x 15

1...15 x 15

High-Static

1...15 x 15

1...15 x 15

1...15 x 15

Type Drive

Standard

Belt

Belt

Belt

High-Static

Belt

Belt

Belt

Nominal Cfm

3000

3400

4000

Maximum Continuous Bhp

Standard

2.90

2.90

3.70

High-Static

4.20

4.20

5.25

Motor Frame Size

Standard

56

56

56

High-Static

56

56

56

Nominal Rpm

Standard

1725

1725

1725

High-Static

1725

1725

1725

Fan Rpm Range

Standard

730-950

840-1085

860-1080

High-Static

860-1080

860-1080

830-1130

Motor Bearing Type

Ball

Ball

Ball

Maximum Allowable Rpm

2100

2100

2100

Motor Pulley Pitch Diameter Min/Max (in.)

Standard

3.4/4.4

3.4/4.4

4.0/5.0

High-Static

4.0/5.0

4.0/5.0

2.8/3.8

Nominal Motor Shaft Diameter (in.)

Standard

7

/

8

7

/

8

7

/

8

High-Static

7

/

8

7

/

8

7

/

8

Fan Pulley Pitch Diameter (in.)

Standard

8.0

7.0

8.0

High-Static

8.0

8.0

5.8

Belt, Quantity...Type...Length (in.)

Standard

1...A...51

1...A...51

1...A...53

High-Static

1...A...53

1...A...53

1...BX...48

Pulley Center Line Distance (in.)

Standard

16.75-19.25

16.75-19.25

15.85-17.50

High-Static

16.75-19.25

16.75-19.25

15.85-17.50

Speed Change per Full Turn of

Movable Pulley Flange (rpm)

Standard

45

45

45

High-Static

45

45

60

Movable Pulley Maximum Full

Turns from Closed Position

Standard

5

5

5

High-Static

5

5

6

Factory Setting

Standard

5

5

5

High-Static

5

5

5

Factory Speed Setting (rpm)

Standard

730

840

860

High-Static

860

860

887

Fan Shaft Diameter at Pulley (in.)

1

1

1

INDOOR COIL

Enhanced Copper Tubes, Aluminum Double-Wavy Fins,

Acutrol Metering Device

Rows...Fins/in.

3...15

4...15

4...15

Total Face Area (sq ft)

8.9

11.1

11.1

HIGH-PRESSURE SWITCH (psig)

Standard Compressor Internal Relief

625

Cutout

428

Reset (Auto.)

320

LOSS-OF-CHARGE/LOW-PRESSURE SWITCH (Liquid Line) (psig)

Cutout

7 ± 3

Reset (Auto.)

22 ± 5

FREEZE PROTECTION THERMOSTAT

Opens (F)

30

Closes (F)

45

OUTDOOR-AIR INLET SCREEN

Cleanable. Screen size and quantity vary by option selected.

RETURN-AIR FILTERS

Throwaway

Quantity...Size (in.)

4...16 x 20 x 2

4...20 x 20 x 2

Bhp