Blue Sea Systems 8379 DC Main + 20 Positions, White Toggle User Manual

Installation, Dc power distribution panel, Warning

Advertising
background image

1. Disconnect all AC and DC power

Disconnect all AC power originating on or off the vessel. This includes

inverters, generators, shore power attachments and any other device

capable of supplying AC power to the ship’s circuits.

Disconnect the main positive DC cable from all batteries to eliminate the

possibility of a short circuit and to disable the inverter while installing the

distribution

panel.

2. Apply Voltage Label

All panel components are sized for 12 or 24 Volt systems. Use the labels

provided to permanently identify the system voltage and its type (DC) as

required by ABYC. Apply the appropriate voltage label to the recessed

area on the front of the panel.

3. Select mounting location and cut opening

If this panel is to serve as your main shore power disconnect circuit

breaker, select a location which is not more then 10 feet from the shore

power inlet or the electrical attachment point of a permanently installed

shore power cord as measured along the conductors of the feed wires. If

it is more then 10 feet additional fuses or circuit breakers must be

installed within 10 feet of the shore power inlet.

Select a mounting location which is protected from water on the panel

front and back and is not in an area where fl ammable vapors from

propane, gas or lead acid batteries accumulate. The circuit breakers

used in marine electrical panels are not ignition protected and may ignite

such

vapors.

Using the panel template provided, make a cutout in the mounting

surface where the distribution panel is to be mounted. Do not yet fasten

the panel to the mounting surface.

4. Select positive feed wire and negative return

Determine the positive feed (red) and negative return (black or yellow)

wire size by calculating the total amperage of the circuits that will be

routed through the panel. Blue Sea Systems’ electrical panels are rated

Marine Electrical Products

DC Power Distribution Panel

PN 8379 / PN 3379 / PN 8382 / PN 3382

Panel Specifi cations

Material:

0.125” 5052-H32 Aluminum Alloy

Primary Finish:

Chemical Treatment per Mil Spec C-5541C

Final Panel Finish: Graphite color 2 part textured Polyurethane
Amperage Rating: All components are sized for 100 Amps of

continuous current

Voltage Rating:

12 or 24 Volt DC*
* Confi gure your panel with the supplied voltage

identifi cation labels.

PN Inches

Millimeters

Overall Dimensions: 8379/3379 14-3/4 x 7-1/2

374.65 x 190.50

8382/3372 14-3/4 x 11-1/4

374.65 x 254.00

Panel Features

8379 / 3379
• One 100 Ampere C-Series DC main circuit breaker
• Twenty circuit breaker positions, Fourteen 15 Ampere branch

circuit

breakers

installed

• DC digital multimeter PN 8248 with 3 position switch for multiple
battery banks and remote shunt

8382 / 3382
• One 100 Ampere C-Series DC main circuit breaker
• Thirty-fi ve circuit breaker positions, Twenty-six 15 Ampere branch
circuit

breakers

installed

• DC digital multimeter PN 8248 with 3 position switch for multiple
battery banks and remote shunt

Page 1 of 3

WARNING

@

It is not possible within the scope of these instructions to fully acquaint

the installer with all the knowledge of electrical systems that may be
necessary to correctly install this product. If the installer is not

knowledgeable in electrical systems we recommend that an electrical
professional be retained to make the installation.

@

If either the panel front or back is to be exposed to water it must be

protected with a waterproof shield.

@

The panels must not be installed in explosive environments such as gas

engine rooms or battery compartments as the circuit breakers are not
ignition

proof.

@

The main positive connection must be disconnected at the battery post to

avoid the possibility of a short circuit during the installation of this
distribution

panel.

@

The shunt must be installed in the negative line to avoid damage to the

meter. Positive voltage applied to digital meter terminals #4 and #5 will
cause damage to the meter not covered by warranty.

@

The vessel’s shore power cord must be disconnected form shoreside

power before installing this electrical panel.

@

If an inverter is installed on the vessel its power leads must be

disconnected at the battery before the panel installation. Be aware that
many inverters have a “sleep mode” in which their voltage potential may
not be detectable with measuring equipment.

@

If an AC Generator is installed aboard it must be stopped and rendered

inoperable before the panel is installed.

@

Verify that no other AC source is connected to the vessels’ wiring before

the panel is installed.

Blue Sea Systems Inc.

Phone (360) 738-8230

425 Sequoia Drive

Fax (360) 734-4195

Bellingham, WA 98226 USA

E-mail [email protected]

www.bluesea.com

at 100 amp total capacity. The positive feed wire must be sized for 3%

voltage drop at the 100 amp panel rating or the maximum amperage

that will be routed through the panel in any particular installation, which

ever is less. It is recommended that the positive feed wire be sized for

the full panel capacity, which, in most cases, will require at least 2 AWG

wire, assuming a 10 foot wire run between the panel and the batteries in

12 volt systems. Refer to the Wire Sizing Chart for other situations. In the

case of panels with two or more columns of breakers, jumpers from

positive bus to positive bus and from negative bus to negative bus

should be the same size as the positive feed and the negative return

wires.

Remember that the length of the circuit is the total of the positive wire

from the power source and the negative wire back to the DC Negative

Bus. Be certain that there is a fuse or circuit breaker of the correct size

protecting the positive feed wire.

5. Install shunt, negative return and positive feed

The DC digital meter shunt must be installed in the negative line of the

circuit whose current is to be measured. Refer to the DC meter

installation and operation manual prior to installing the shunt. Review the

Theory of Operation, Use, Installation Overview, Installing Shunt, Wiring

Diagram and Wire by Wire Instruction sections. Observe all warning

regarding the shunt installation.

Connect a negative return wire from the negative bus on the panel to DC

negative and ultimately the load side of the shunt. Connect a positive

feed wire from the positive bus on the panel to DC positive. Be certain

that there is a fuse or circuit breaker of the correct size protecting the

positive feed wire.

6. Install battery bank voltage monitor wires

The panel is supplied with a digital meter and switch to monitor the

voltage of three separate sources, usually the batteries. Connect a

minimum 16 AWG red wire from each source to be monitored to each of

the corresponding input wires of the switch. There should be a 1 ampere

fuse in each positive wire near each source.

Installation

Document 6675 Rev.E