Blue Sea Systems 8176 AC Main + 11 Positions [European] User Manual

Installation, Ac main power distribution panels, Warning

Advertising
background image

Marine Electrical Products

PN 8076 / PN 3076 / PN 8176 / PN 3176

AC Main + 11 Position

Panel Specifi cations

Voltage Rating:

PN 8076 / PN 3076 120 Volts AC

PN 8176 / PN 3176 230 Volts AC

Panels are rated for these voltages and are so
marked in order to comply with ABYC standards.

Amperage Rating: Panel Buses are sized for 100 Amperes of

continuous current.

Material:

0.125” 5052-H32 Aluminum Alloy

Primary Finish:

Chemical Treatment per Mil Spec C-5541C

Final Panel Finish: Graphite color 2 part textured Polyurethane

Inches

Millimeters

Panel Depth:

3-1/2

88.90

Overall Dimensions: 10-1/2 x 7-1/2

266.70 x 190.50

Mounting Centers: 9-11/16 x 6-11/16 246.10 x 169.90

Panel Features

PN 8076/PN 3076-120 Volt AC
• One double-pole 30 Ampere AC main circuit breaker
• Eight 15 Ampere branch circuit breakers installed
• 0-150 Volt AC Voltmeter
• 0-50 Ampere AC Ammeter

PN 8176/PN 3176-230 Volt AC
• One double-pole 16 Ampere AC main circuit breaker
• Eight 8 Ampere branch circuit breakers installed
• 0-250 Volt AC Voltmeter
• 0-50 Ampere AC Ammeter

Blue Sea Systems Inc.

Phone (360) 738-8230

425 Sequoia Drive

Fax (360) 734-4195

Bellingham, WA 98226 USA

E-mail [email protected]

www.bluesea.com

Document 9641 Rev.E

WARNING

@

It is not possible within the scope of these instructions to fully acquaint

the installer with all the knowledge of electrical systems that may be

necessary to correctly install this product. If the installer is not

knowledgeable in electrical systems we strongly recommend that an

electrical professional be retained to make the installation.

@

If either the panel front or back is to be exposed to water it must be

protected with a waterproof shield.

@

The panels must not be installed in explosive environments such as

gas engine rooms or battery compartments as the circuit breakers are

not ignition proof.

@

The vessel’s shore power cord must be disconnected form shoreside

power before installing this electrical panel.

@

If an inverter is installed on the vessel its power leads must be

disconnected at the battery before the panel installation. Be aware that

many inverters have a “sleep mode” in which their voltage potential

may not be detectable with measuring equipment.

@

If an AC Generator is installed aboard it must be stopped and rendered

inoperable before the panel is installed.

@

Verify that no other AC source is connected to the vessel’s wiring

before the panel is installed.

Guarantee

Any Blue Sea Systems product with which a customer is not satisfi ed
may be returned for a refund or replacement at any time.

Installation

1. Disconnect all AC and DC power

Disconnect all AC power originating on or off the vessel. This includes

inverters, generators, shore power attachments and any other device

capable of supplying AC power to the ship’s circuits.

Disconnect the main positive DC cable from all batteries to eliminate

the possibility of a short circuit and to disable the inverter while

installing the distribution panel.

2. Select mounting location and cut opening

If this panel is to serve as your main shore power disconnect circuit

breaker, select a location which is not more then 10 feet from the shore

power inlet or the electrical attachment point of a permanently installed

shore power cord as measured along the conductors of the feed wires.

If it is more then 10 feet additional fuses or circuit breakers must be

installed within 10 feet of the shore power inlet.

Select a mounting location which is protected from water on the panel

front and back and is not in an area where fl ammable vapors from

propane, gasoline or lead acid batteries accumulate. The circuit

breakers used in marine electrical panels are not ignition protected and

may ignite such vapors.

Using the panel template provided, make a cut out in the mounting

surface where the distribution panel is to be mounted. Do not yet

fasten the panel to the mounting surface.

3. Install branch circuit wires

Determine the proper wire size for each branch circuit using the wire

sizing chart. Verify that the standard circuit breakers installed in the

panel are correct for each branch circuit. Remove and replace any that

are incorrectly sized. The circuit breaker must have a rating less than

the allowable amperage of the wire, yet greater than the circuit’s

continuous

current.

AC Main Power Distribution Panels

Connect each branch circuit hot (black) to the appropriate load
terminal. Connect each branch circuit neutral (white) to one of the
screws on the neutral bus. Connect each branch safety ground wire
(green) to one of the screws of the safety ground bus.

Do not confuse the neutral current carrying wires (sometimes called
ground) with the green normally non-current carrying wires (sometimes
called grounding). These two wires must be connected only at the
source of power, nowhere else.

Wire sizing chart

Use the wire sizing chart below to determine the proper branch and

feed circuit wire sizes.

Allowable Amperage of Conductors

Note:

This chart assumes wire with 105°C insulation rating

and no more than 2 conductors are bundled.

Not suitable for sizing fl exible shore power cords.