Connection example
The following connection example shows a possible circuit structure with redundant design at the cable level as
well.
The signals of the emergency stop chain are evaluated by a safety relay (ESM from EUCHNER).
The overall control concept into which the pull rope switch RPS is integrated must be evaluated by the end
consumer/machine designer in accordance with EN ISO 13849-2.