When installing and adjusting the rope pull switch, it is necessary to take into account the physical changes in
the rope length as a result of variations in temperature.
Table 3 shows the permitted rope tension lengths as a function of the expected temperature difference.

The diagram also shows the maximum permitted rope tension length for the different spring forces of the
respective switch types. It also permits selection of the appropriate switch corresponding to the expected
temperature variations.



Table 3

Rope tension length Lmax. in meters [m]

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

22

24

26

28

30

32

34

36

38

40

42

44

46

48

50

55

60

65

70

75

+/-40 K

+/-35 K

+/-30 K

+/-25 K

+/-20 K

+/-15 K

+/-10 K

+/-5 K

Max. temperature

fl

uctuati

on i

n

Kelvin

+/-3.5 K

RPS...100

Rope tension length max. 25 m

RPS...175

Rope tension length max. 37.5 m

RPS...300

Rope tension length max. 75 m

Rope supports must be provided at intervals of 2–5 m when planning and installing the system. Refer also to
the section Safety precautions.