In order to maintain consistency, this device type will only allow connections to
either INT or REAL based Assembly instances (

→ Data Type definition  19).

Once a valid connection is established, attempts to configure connections to a
different type of Assembly instance will return an error.
The I/O Assembly DATA attribute has the format shown below:

Instance

Type

Byte Bit 0 … 7

1

Input

0

INT Pressure Value (low byte)

1

2

Input

0

Exception Status; Class 48, Instance 1, Attribute 12

1

INT Pressure Value (low byte)

2

Class 49, Active Value

4

Input

0

REAL Pressure Value (low byte)

1
2

Class 49, Active Instance Value

3

5

Input

0

Exception Status Class 48, Instance 1, Attribute 12

1

REAL Pressure Value (low byte)

2

Class 49, Active Instance Value

3
4

8

Input

0

Exception Status ; Class 48, Instance 1, Attribute 12

9

0

Active Instance

1
2

INT Active Pressure Value

3

10

Input

0

Exception Status

1

Active Instance

2
3

INT Active Pressure Value

4

12

Input

0

Active Instance

1
2

REAL Pressure Value

3
4
5

13

Input

0

Exception Status

1

Active Instance

2
3

REAL Pressure Value

4
5
6

3.2 I/O Assembly Object