Operator responsibility – Safety instructions

10


Safety installations
(adjustable via LED):
High temperature protection

°C -25 ... 85

Low temperature protection

°C -25 ... 85

Low liquid level protection

float switch

Classification according to DIN 12876-1

III

Overload protection for pump motor

contactor

Overload protection for cooling compressorcontactor
Alarm signal

optical + audible



Environmental conditions according to IEC 61 010-1:

Use only indoor.

Altitude up to 2000 m - normal zero.

Ambient temperature: +5 ... +40 °C

Air

humidity:

Max. rel. humidity 80 % for temperatures up to +31 °C,

linear decrease down to 50 % relative humidity at a temperature of +40 °C

Max. mains fluctuations of ±10 % are permissible.


The unit corresponds to Class I
Overvoltage category

II

Pollution degree

2

Caution:

The unit is not for use in explosive environment.


Standards for interference resistance according to EN 61326-1
This unit is an ISM device classified in Group 1 (using high frequency for internal purposes)
Class A (industrial and commercial range).