JULABO FCW1600_1600S Recirculating coolers User Manual

Page 11

Advertising
background image

Recirculating coolers

11

2.5.

Cooling water connection

Only for water cooled models - FCW:

Cooling water pressure (IN / OUT )

max.

6 bar

Difference pressure (IN - OUT )

3.5 to 6 bar

Cooling water temperature

<20 °C

Recommended quality of cooling water:

pH – value

7,5 to 9,0

Sulfate [SO4 2- ]

< 100 ppm

Hydrocarbonate [HCO3- ] / Sulphate [SO4 2-]

> 1 ppm

Hardness [Ca2+, Mg2+] / [HCO3-]

> 0,5 dH

Alkalinity

60 ppm < [HCO3-] < 300 ppm

Conductivity

< 500 μs / cm

Chloride (CL-)

< 50 ppm

Phosphate (PO43-)

< 2 ppm

Ammonia (NH3)

< 0,5 ppm

Free Chlorine

< 0,5 ppm

Ferri Ions (Fe3+ )

< 0,5 ppm

Mangano Ions (Mn2+)

< 0,05 ppm

Carbon dioxide (CO2)

< 10 ppm

Hydrosulfide (H2S)

< 50 ppm

Content of oxygen

< 0,1 ppm

Algae growth

impermissible

Suspended solids

impermissible

Notice:

Danger of corrosion of heat exchanger due to unsuitable quality of
cooling water.

 Due to its high content of lime hart water is not suitable for cooling and

causes calcination of the heat exchanger.

 Ferrous water or water containing ferrous particles will cause formation of

rust even in heat exchangers made of stainless steel.

 Chlorous water will cause pitting corrosion in heat exchangers made of

stainless steel.

 Due to its corrosive characteristics distilled and deionized water is

unsuitable and will cause corrosion of the bath. .

 Due to its corrosive characteristics sea water is not suitable.
 Due to its microbiological (bacteria) components which settle in the heat

exchanger untreated and unpurified river water and water from cooling
towers is unsuitable.

 Avoid particulate matter in cooling water.
 Avoid putrid water.

Advertising