6 Configuration

32

6.2

Analog inputs

The eight analog inputs are measuring inputs for RTD temperature probes in 2-wire circuit.

Setup dialog

Parameter

Parameter

Selection/settings

Description

Sensor

Selection of measuring probe for the relevant analog input

No choice

No sensor selected

RTD temp. probe 2-w

RTD temperature probe in 2-wire circuit

Linearization

Available options and factory settings depend on the measuring probe selected.

Linear

Pt100

DIN EN 60751

Pt500

DIN EN 60751

Pt1000

DIN EN 60751

Pt100J

JIS 1604

Pt100G

GOST 6651-94

Scale

start

Factory setting depends on the linearization.

-99999 to +99999

Start value of display range

Scale

end

Factory setting depends on the linearization.

-99999 to +99999

End value of display range

TAG number

7 characters

Identification marking (documentation in
PLC)

Unit

5 characters (%)

Unit for numerical representation of
measured value