2 analog inputs, Analog inputs, 6 configuration – JUMO 705021 mTRON T - Analog Input Module, 8-Ch. Operating Manual User Manual
Page 32

6 Configuration
32
6.2
Analog inputs
The eight analog inputs are measuring inputs for RTD temperature probes in 2-wire circuit.
Setup dialog
Parameter
Parameter
Selection/settings
Description
Sensor
Selection of measuring probe for the relevant analog input
No choice
No sensor selected
RTD temp. probe 2-w
RTD temperature probe in 2-wire circuit
Linearization
Available options and factory settings depend on the measuring probe selected.
Linear
Pt100
DIN EN 60751
Pt500
DIN EN 60751
Pt1000
DIN EN 60751
Pt100J
JIS 1604
Pt100G
GOST 6651-94
Scale
start
Factory setting depends on the linearization.
-99999 to +99999
Start value of display range
Scale
end
Factory setting depends on the linearization.
-99999 to +99999
End value of display range
TAG number
7 characters
Identification marking (documentation in
PLC)
Unit
5 characters (%)
Unit for numerical representation of
measured value