6 configuration – JUMO 705021 mTRON T - Analog Input Module, 8-Ch. Operating Manual User Manual

Page 33

Advertising
background image

33

6 Configuration

Offset type

To offset plant-specific deviations, the measured value can be offset for each analog input.
When doing this, the offset type is used to specify the type of measured value offset.
"Standardized" offset type: The measured value is offset after linearization (temperature value
in °C or °F).
"Physical" offset type: The physical measured value is offset before linearization (resistance
in ohms).
A typical application scenario for the "physical" offset type is compensation of the lead wire re-
sistance when using an RTD temperature probe.

Offset

A positive or negative form of the correction value is added to the measured value (entering a
negative correction value reduces the measured value).

Filter time constant

The filter time constant is used to adjust the digital input filter (2nd order filter). If the input signal
changes suddenly, approx. 26 % of the change is recorded following a period that corresponds
to the filter time constant (2 × filter time constants: approx. 59 %; 5 × filter time constants:
approx. 96 %). A large filter time constant means a high level of attenuation of interference sig-
nals, a slow reaction time of the actual value display, and low limit frequency (low-pass filter).

Status after change of configuration

The input values before the change of configuration are not saved; the new input values are
available approx. 2 seconds after the change of configuration.

Behavior after power on

All analog inputs are initialized and start their measurements over (no statuses are saved with
power off).

Offset type

Type of measured value offset

Standardized

Offset of standardized measured value
(after linearization)

Physical

Offset of physical measured value
(before linearization)

Offset

-100 to 0 to +100

Correction value

Filter time con-
stant

0 s to 0.6 s to 100 s

Time constant for adjusting the digital
input filter (0 s = filter off)

Parameter

Selection/settings

Description

?

?

?