4 Electrical connection
26
4.3.2
Analog inputs
Connection
Input
Terminals
Symbol and terminal designation
Thermocouple
1
2
3
4
2 and 3
6 and 7
10 and 11
14 and 15
2, 6, 10, 14
3, 7, 11, 15
RTD temperature probe
2-wire circuit
1
2
3
4
2 and 4
6 and 8
10 and 12
14 and 16
2, 6, 10, 14
4, 8, 12, 16
RTD temperature probe
3-wire circuit
1
2
3
4
2 to 4
6 to 8
10 to 12
14 to 16
2, 6, 10, 14
3, 7, 11, 15
4, 8, 12, 16
RTD temperature probe
4-wire circuit
1
2
3
4
1 to 4
5 to 8
9 to 12
13 to 16
1, 5, 9, 13
2, 6, 10, 14
3, 7, 11, 15
4, 8, 12, 16
Voltage DC 0(2) to 10 V
1
2
3
4
1 and 2
5 and 6
9 and 10
13 and 14
1, 5, 9, 13
2, 6, 10, 14
Voltage DC 0 to 1 V
1
2
3
4
2 and 3
6 and 7
10 and 11
14 and 15
2, 6, 10, 14
3, 7, 11, 15
Current DC 0(4) to 20 mA
1
2
3
4
3 and 4
7 and 8
11 and 12
15 and 16
3, 7, 11, 15
4, 8, 12, 16
Resistance transmitter
A = Start
E = End
S = Slider
1
2
3
4
2 to 4
6 to 8
10 to 12
14 to 16
2, 6, 10, 14
3, 7, 11, 15
4, 8, 12, 16
Resistance/potentiometer
2-wire circuit
1
2
3
4
2 and 4
6 and 8
10 and 12
14 and 16
2, 6, 10, 14
4, 8, 12, 16
Resistance/potentiometer
3-wire circuit
1
2
3
4
2 to 4
6 to 8
10 to 12
14 to 16
2, 6, 10, 14
3, 7, 11, 15
4, 8, 12, 16
U
+
-
x
U
+
-
x
I
+
-
x
E
S
A