6 Configuration
44
Signal suppression
When signal suppression is active, the input signal and the inverting and delay parameters are
irrelevant. In this case, a fixed signal with a configurable level is issued (to the system bus).
Event text
Setup program: Selection of text from a list
Click the "..." button to open a list with the text numbers and the associated texts. The texts can
be edited.
Multifunction panel: Selection of text using the text number
The setup program is required to view and edit the texts.
Status after change of configuration
The output signal to the system bus always adopts the status that corresponds to the current
configuration.
Behavior after power on
After initialization, the input signals are available immediately, according to their configuration.
Event text
Use default text or select other text from
the list.
Text that is entered in the event list for
an alarm (if Alarm type = "Event").
Parameter
Selection/settings
Description
?