4 electrical connection, 1 safety information, Electrical connection – JUMO 707050 dTRANS T05 - Programmable 2-Wire Transmitter Operating Manual User Manual
Page 53: Safety information

15
4 Electrical connection
4.1
Safety information
•
The electrical connection must only be carried out by qualified personnel.
•
When mounting, connecting, and operating the transmitter, ensure that no electrostatic
charging can take place.
•
The transmitter is not suitable for installation and application areas with an explosion haz-
ard.
•
Never expose the transmitter to magnetic or electrical fields (e.g. caused by transformers,
walkie-talkies, or electrostatic discharge).
•
An electrical connection that deviates from the connection diagram can destroy the trans-
mitter.
•
The transmitter is suitable for use in SELV or PELV current circuits according to protection
rating 3. The case implements basic insulation of up to 50 V towards neighboring devices.
4.2
Terminal assignment and dimensions (mm) of
dTRANS T05 B
5
Ш
44
Ш
7
Ш
33
21
Connection for
Terminal assignment
Voltage supply
Type 707050
R
B
= (V
b
- 11 V)/22 mA
DC 11 to 35 V
Current output
R
B
= Load resistance
4 to 20 mA
V
b
= Voltage supply
2
1
+
–