Installation, Figure 4: connector wiring diagram – Lenze ESVZAR0 RS-485 User Manual

Page 10

Advertising
background image

8

CMVMB401C

Installation

3.2

RS-485 Terminal Block
Table 3 describes the RS-485 terminal block. The 5 pole connector provides 2-wire connection to the network.

Table 3: RS-485 Terminal Block

Terminal Description

Important

Connector

1

Earth ground /
shield

For reliable communication make sure terminal is
connected to the Modbus network GND/common.
If only two wires are used (TXA and TXB) in the
network, connect Terminal 1 to chassis/earth GND.

1 2

3 4

5

2

TXA

If controller is located at either end of the network,
a terminating resistor (120ohm typical) should be
connected across TXA and TXB

3

No connection

4

TXB

5

No connection

Protection against contact
• All terminals have basic isolation (single insulating distance)
• Protection against contact can only be ensured by additional measures (i.e. double insulation)

3.3

Electrical Installation

3.3.1 Cable Types

For RS-485 Modbus networks, use a quality shielded twisted pair cable. The use of low quality cable will result in
excess signal attenuation and data loss.

3.3.2 Connections and Shielding

To ensure good system noise immunity all networks cables should be correctly grounded:
• Minimum grounding recommendation: ground the network cable once in every cubical.
• Ideal grounding recommendation: ground the network cable on or as near to each drive as possible.
• For wiring of cable to the connector plug the unscreened cable cores should be kept as short as possible;

recommended maximum of 20mm. The shield connection of terminal 1 should also be wired to earth (PE).

20mm

max

Connect to
drive earth

(PE)

1

2

3

4

5

Figure 4: Connector Wiring Diagram