Extended Parameters

4

Extended Parameters for Modbus RTU

In addition to the drive parameters that are detailed in the Operating Instructions (SV01), the installation of the
RS485/Modbus RTU module will give access to the 400 series parameters that are exclusive to this communication
module. Table 4 lists these 400 Series parameters.

4.1

Parameter Menu

Table 4: 400 Series Parameters for Modbus RTU Operation

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

RS485/Modbus: Modbus Module Specific parameters

P400

Network Protocol

0 Not Active
1 Remote Keypad
2 Modbus RTU

P401

Module Revision

01.0.0 Display reads 01.x.x where:

01 = RS485/Modbus Module
x.x = Module Revision

Read only

P402

Module Status

0

0 Not Initialized

Read only
Online state “3” indicates that the communications between
the drive and module are working properly.

1 Initialization: Module to EPM
2 Initialization: EPM to Module
3 Online
4 Failed Initialization Error
5 Time-out Error
6 Initialization Failed

Module type mismatch (P401)

7 Initialization Error

Protocol Selection mismatch (P400)

P403

Module Reset

0

0 No Action

1 Reset Module parameter values to default.

Returns module parameters 401…499 to the default values
shown in this manual.

P404

Module Time-out
Action

3

0 Ignore

• Action to be taken in the event of a Module/Drive Time-

out.

• Time-out is fixed at 200ms.
• Selection 1 (STOP) is by the method selected in P111.

1 STOP (see P111)
2 Quick Stop

3 Fault ( n )

P405

Network Fault

0

0 No Fault

Read only, see P425 and P426

1 Network Time-out, n

P406

Proprietary

Manufacturer specific

Read only

RS485/Modbus: System bus parameters

P410

Network address

1

1

247

The Drive does not support the Modbus “broadcast”
function.

P411

Network
Baud Rate

2

0 2400 bps
1 4800 bps
2 9600 bps
3 19200 bps
4 38400 bps
5 57600 bps
6 115200 bps

P412

Network Data
Format

0

0 8 Data bits, No Parity, 2 stop bits
1 8 Data bits, No Parity, 1 stop bit
2 8 Data bits, Even Parity, 1 stop bit
3 8 Data bits, Odd Parity, 1 stop bit