Lenze ESVZAR0 RS-485 User Manual

Page 28

Advertising
background image

26

CMVMB401C

Drive Registers

9.2.13 Parameter Version - Register #50

The Parameter Version identifies the parameter set for the current version of software. If the Parameter version is
different between two drives, it could indicate that a register has been added or deleted, a register’s min/max limits
have changed, a register’s function has been changed, or a register’s default value has been changed.

9.2.14 Network Controlled Digital Output - Register #70

To control the state of the relay or digital output (TB14), Drive Programming Parameter P140 and/or P142 must be
set to 25 (Network Controlled).

9.2.15 Network Controlled Analog Output - Register #71

To control the state of the analog output (TB30), Drive Programming Parameter P150 must be set to 09 (Network
Controlled).