CMVMB401C

Drive Registers

9.2.5 Run Status - Register #26

The low byte (DL) of register 26 provides the Operational Status as listed in Table 9.

Table 9: Operational Status - Register #26 DL

Value

Description

0

Fault Lockout

1

Fault

2

Start Pending

3

IDE not done

4

Inhibit

5

STOP

6

Lower Transistors switching on

7

Run IDE

8

Run

9

Accel

10

Decel

11

Decel Override

12

DC Brake

13

Flying Restart

14

Slow Current Limit

15

Fast Current Limit

16

Sleep

9.2.6 Actual Direction - Register #27

The high byte (DH) of register 27 provides the actual rotational direction of the motor.

Table 10: Actual Rotational Direction - Register #27 DH

Setting

Direction

0

Forward

1

Reverse

9.2.7 Control Mode - Register #27

The low byte (DL) of register 27 provides the Control Mode as listed in Table 11.

Table 11: Control Mode - Register #27 DL

Value

Control Mode

Description

0

Local

Start commands from drive keypad (P100 = 0 or 4)

1

Terminal

Start commands from control wiring on drive terminal Strip (P100 = 1, 4 or 5)

2

Remote Keypad Only

Start commands from optional remote keypad (P100 = 2 or 5)

3

Network Only

Start commands from Network, but Network control is not active (P100 = 3)

4

Network Control

Start commands from Network and Network control is active (P100 = 0, 1, 3 or 4)