Technical data

General data and operating conditions
Other application conditions

3

l

16

BA 13.0008 − EN 2.1

3.2.1

Other application conditions

ƒ

Other application conditions require a power derating or torque reduction using the
factors listed in table 2 and 3 (see below).

1

2

0

0 Installation height

1 Permissible continuous torque M

perm

/M

cont

40 °C 1000 m

2 Cooling air / ambient temperature [°C]

(

Stop!

ƒ

The motor will be destroyed when the maximum motor speed is exceeded

ƒ

Do not exceed the maximum torques specified in Tab. 2!
– Torques as high as indicated can be reached through appropriate

motor−controller combinations.

– Excessive torques might result in a break of the motor shaft!

)

Note!

ƒ

Excessive axial and radial forces reduce the bearing service life.
Observe the permissible forces to Tab. 2!
– Calculation basis:

Bearing service life L

h10

= 10000 h

Torque M = 2.5 M

r

The permissible continuous power is calculated as follows:

P

= k

υ

@ k

h

@ P

c

with P

c

being the permissible continuous power under normal conditions. A

corresponding relation applies to the torque:
M’

= k

υ

@ k

h

@ M

c

with M

c

being the permissible continuous torque under normal conditions.