EDS84AYCER EN 2.0 - 11/2010
L
31
E84AYCER communication manual (PROFINET)
Installation
Electrical installation
Colour code of the Ethernet cable
[5-10] Ethernet connector in accordance with EIA/TIA 568A/568B
Note!
The wiring and colour code are standardised in EIA/TIA 568A/568B.
According to the industrial standard, the use of 4-pin Ethernet cables is
permissible. The cable type only connects the assigned pins 1, 2, 3 and 6 to one
another.
E94YCEI004A
Pair
Pin
Signal
EIA/TIA 568A
EIA/TIA 568B
3
1
Tx +
White / green
White / orange
2
Tx -
Green
Orange
2
3
Rx +
White / orange
White / green
1
4
Blue
Blue
5
White / blue
Blue / white
2
6
Rx -
Orange
Green
4
7
White / brown
White / brown
8
Brown
Brown