Electrical installation

Wiring according to EMC

In typical systems, standard shielding of the Ethernet cables is sufficient.

In environments with a very high level of interference, immunity to noise can be improved
by additionally earthing the cable shield on both sides.

Observe the following notes for this:
1. The clearance of the additional earthing from the Ethernet plug depends on the

module slot. The clearance is
– approx. 10 cm for the upper slot (MXI1);
– approx. 20 cm for the lower slot (MXI2).

2. Starting from this clearance, remove the plastic sheath of the cable on a length of

2 cm.

3. Mount the cable shield on the shield sheet of the Servo Drive 9400.

E94YCXX008

0

Connection to the shield sheet of the Servo Drive 9400

1

Continuing EtherCAT cable at X247 (OUT)

2

Incoming EtherCAT cable at X246 (IN)

3

Communication module in slot MXI1 of the Servo Drive 9400