8diagnostics, Led status displays, H1_diagnose−status_leds_e94aycet – Lenze E94AYCET User Manual

Page 42

Advertising
background image

8

Diagnostics

LED status displays

EDK94AYCET DE/EN/FR/ES/IT 5.0

42

l

H1_Diagnose−status_LEDs_E94AYCET

Description

LED

Description

Condition

Colour

Pos.

RUN

green

off

The communication module is not active on the fieldbus or is in
the "Init" status.

blinking

200 ms

200 ms

"Pre−operational" status active:

l

Access to parameters and objects possible.

l

No process data exchange

blinking
once
(single
flash)

1000 ms

200 ms

200 ms

1000 ms

"Safe−operational" status active:

l

The data are not active in the standard device yet.

on

The communication module is in the "Operational" status.

ERR

red

off

No error

blinking

200 ms

200 ms

The configuration is invalid/faulty.

blinking
once
(single
flash)

1000 ms

200 ms

200 ms

1000 ms

l

A state change that was not requested has occurred. (The
slave application has changed the EtherCAT status
independently.)

l

Synchronisation error (The EtherCAT node changes to the
"Safe−operational" status automatically.)

blinking
twice
(double
flash)

200 ms

200 ms

1000 ms

200 ms

200 ms

200 ms

200 ms

An "Application Watchdog Timeout" or a "Sync Manager
Watchdog Timeout" has occurred.

DE

red

on

The communication module is not accepted by the standard
device, or the standard device is not active. (See notes in the
documentation for the standard device.)