Technical data

Rated data

4

l

37

EDK94ZMR47XDB DE/EN/FR/ES/IT 4.0

Mounting conditions

Mounting place

In the control cabinet

Mounting position

Vertically

Free space

The required free space results from the mounting position
and the specifications of the standard device.

4.2

Rated data

Mains

Voltage

Voltage range

Frequency range

U

Lrated

[V]

U

Lrated

[V]

f [Hz]

3/PE AC

230

180 − 0 % ... 264 + 0 %

45 − 0 % ... 65 + 0 %

3/PE AC

400

320 − 0 % ... 440 + 0 %

45 − 0 % ... 65 + 0 %

3/PE AC

500

400 − 0 % ... 550 + 0 %

45 − 0 % ... 65 + 0 %

Voltage

Frequency

Rated current [A]

Number of

phases

[V]

[Hz]

up to +45 °C



up to +55 °C



E94AZMR0264xDB

230/400/500

50/60

26/26/26

19/19/19

3

E94AZMR0474xDB

230/400/500

50/60

47/47/47

35/35/35

3

 Temperature in the control cabinet

Power loss

Inductance

Regenerative

inductance

Voltage drop

P

V

[W]

L [mH]

L

gen

[mH]

DU [V]

E94AZMR0264SDB

65

0.77

±10 %

0.84

±10 %

6.3

E94AZMR0264LDB

72

E94AZMR0474SDB

85

0.42

±10 %

1.54

±10 %

6.2

E94AZMR0474LDB

101