Rated data
Mains
Voltage
Voltage range
Frequency range
U
Lrated
[V]
U
Lrated
[V]
f [Hz]
3/PE AC
230
180 − 0 % ... 264 + 0 %
45 − 0 % ... 65 + 0 %
3/PE AC
400
320 − 0 % ... 440 + 0 %
45 − 0 % ... 65 + 0 %
3/PE AC
500
400 − 0 % ... 550 + 0 %
45 − 0 % ... 65 + 0 %
Voltage
Frequency
Rated current [A]
Number of
phases
[V]
[Hz]
up to +45 °C
up to +55 °C
E94AZMR0264xDB
230/400/500
50/60
26/26/26
19/19/19
3
E94AZMR0474xDB
230/400/500
50/60
47/47/47
35/35/35
3
Temperature in the control cabinet
Power loss
Inductance
Regenerative
inductance
Voltage drop
P
V
[W]
L [mH]
L
gen
[mH]
DU [V]
E94AZMR0264SDB
65
0.77
±10 %
0.84
±10 %
6.3
E94AZMR0264LDB
72
E94AZMR0474SDB
85
0.42
±10 %
1.54
±10 %
6.2
E94AZMR0474LDB
101