Connection data, Electrical installation – Lenze E94AZMR User Manual

Page 48

Advertising
background image

Electrical installation

Connection data

6

l

48

EDK94ZMR47XDB DE/EN/FR/ES/IT 4.0

6.3

Connection data

Mains

Terminal X320

Labelling

Description

L1
L2
L3

Connection of the L1, L2, L3 mains phases

+

Connection for the supply−side PE conductor with M5 ring cable lug

SSP94NF406

Terminal data

Max. conductor cross−section

Tightening torque

!

[mm

2

]

[AWG]

[Nm]

[lb−in]

E94AZMR0264xDB

10

6

1.2 ... 1.5

10.6 ... 13.3

1.0 x 4.0

E94AZMR0474xDB

25

2

2.5

22.1

1.0 x 6.5

PE connection data

Æ

Starting torque

!

[mm]

[Nm]

[lb−in]

E94AZMR0264xDB

M5

3

26.5

PH2

E94AZMR0474xDB

24 V supply

Terminal X323

Labelling

Description

GE

GND external supply

SSP9400X11

24E

24 V external supply through safely separated power supply unit
(SELV/PELV)
IEC 61131−2, 22.8 ... 28.8 V, residual ripple max. ±5 %
Current during operation: 450 mA
Starting current: max. 4 A for 100 ms

Terminal data

Conductor cross−section

Tightening torque

[mm

2

]

[AWG]

[Nm]

[lb−in]

Flexible

0.2 ... 2.5

24 ... 12

Spring terminal

With wire end
ferrule

Stripping length / contact length: 10 mm