Mounting steps – Lenze E94AZMR User Manual

Page 44

Advertising
background image

Mechanical installation

Mounting steps

5

l

44

EDK94ZMR47XDB DE/EN/FR/ES/IT 4.0

5.5

Mounting steps

(

Stop!

Heavy device weight
The device is very heavy and must be lifted for the mounting.
Possible consequences:

ƒ

Injury to persons, particularly backache when lifting and holding the device,
respectively

ƒ

Injury to persons and damage to material assets due to the device falling
down

Protective measures:

ƒ

The device must only be carried with a load bearing system such as an
indoor crane permitted for the device weight

ƒ

Before the transport, the hoist, the load bearing system and lifting
accessories must be checked for sufficient payload and faultless status

ƒ

Do not remove the hoist and the lifting accessories until the device lies safe
on a stable surface or is finally mounted.

Proceed as follows for the installation:

1. Prepare M5 threaded holes on the mounting plate, for instance according to the

mounting grid.
– Always use all mounting points specified.

2. Screw the filter onto the mounting plate.

– Use M5 screw and washer assemblies or M5 hexagon socket screws with washers.
– If further devices are to be mounted directly adjacent on the right−hand side of the

filter, do not tighten the screws fully before all devices are mounted and aligned.

– Tightening torque: 3.4 Nm (30 lb−in).