Electrical installation

Mounting steps

6

l

49

EDK94ZMR47XDB DE/EN/FR/ES/IT 4.0

6.4

Mounting steps

E94AZMR003

How to connect the filter:

1. Connect the following cables to the installation backplane of the regenerative

power supply module; observe documentation of the regenerative power supply
module.
– Filter output cable X321
– Filter output cable X322
– Control cable X324

2. Connect 24−V DC voltage source to terminal X323

– Use safely separated power supply unit (SELV/PELV)

3. Connect mains cable to terminal X320.

4. Mount PE conductor on the supply side with fork−type or ring cable lug M5 to the PE

conductor screw.
– PE connection must comply with EN 61800−5−1 .