Informazioni sulla sicurezza
Informazioni sulla sicurezza per l’installazione secondo la normativa UL o UR
l
101
EDK94PNE36 DE/EN/FR/ES/IT 3.1
2.4
Informazioni sulla sicurezza per l’installazione secondo la normativa U
L
o U
R
J
Warnings!
ƒ
Maximum surrounding air temperature: 55 °C.
ƒ
For use in a pollution degree 2 environment.
ƒ
Branch circuit protection:
Suitable for use on a circuit capable of delivering not more than 5000 rms
symetrical amperes, 500 V max.
ƒ
Voltage of the fuses must at least be suitable with the input voltage of the
drive.
ƒ
Use 60/75 °C copper wire only, except for control circuits.
Branch circuit protection
Tipo
Fusibile [A]
E94APNE0104
15
E94APNE0364
40