Wiring of the standard device 7, 24 v supply, Stripping length / contact length: 10 mm – Lenze E94APNE User Manual

Page 45

Advertising
background image

Wiring of the standard device

7

l

45

EDK94PNE36 DE/EN/FR/ES/IT 3.1

24 V supply

Terminal X11

Labelling

Description

GE

GND external supply

SSP9400X11

24E

24 V external supply through safely separated power supply unit
(SELV/PELV)
IEC 61131−2, 19.2 ... 28.8 V, residual ripple max. ±5 %
Current during operation: 450 mA
Starting current: 4 A for 100 ms

Terminal data

Conductor cross−section

Tightening torque

[mm

2

]

[AWG]

[Nm]

[lb−in]

Flexible

0.2 ... 2.5

24 ... 12

Spring terminal

With wire end
ferrule

Stripping length / contact length: 10 mm

Digital inputs, digital outputs

Terminal X12

Labelling

Description

GOI

GND digital out/in

DI1

External control of the brake chopper for discharge after power−off
(24−V supply at X11 required)

DO1

Mains OK

DO2

Brake chopper active

DO3

Short circuit in brake chopper

SSP9400X12

DO4

Heatsink overtemperature

Terminal data

Conductor cross−section

Tightening torque

[mm

2

]

[AWG]

[Nm]

[lb−in]

Flexible

0.2 ... 2.5

24 ... 12

Spring terminal

With wire end
ferrule

Stripping length / contact length: 10 mm

Advertising