Technical data, General data and operating conditions, 4technical data – Lenze E94AZMS0314 User Manual

Page 38

Advertising
background image

4

Technical data

General data and operating conditions

EDK94AZMS DE/EN/FR/ES/IT 8.0

38

l

H1_Daten−Abmess E94AZMS GG 1−3_en

4

Technical data

General data and operating conditions

Conformity and approval

Approval

UR

UL508

Industrial Control Equipment, Underwriter
Laboratories (File−No. E219022) for USA and Canada

EAC

TP TC 020/2011
(TR CU 020/2011)

Electromagnetic
compatibility of
technical means

Eurasian Conformity
TR CU: Technical Regulation
of Customs Union

EAC

TP TC 004/2011
(TR CU 004/2011)

On safety of low
voltage equipment

Eurasian Conformity
TR CU: Technical Regulation
of Customs Union

Mains data

Mains types

With grounded neutral (TT/TN systems)

Operation permitted without restrictions

Other mains types

Observe instructions for special measures in the
documentation for the basic device!

Protection of persons and equipment

Enclosure

EN 60529

IP20

Not in the wire range of the
terminals

NEMA 250

Protection against
contact to type 1

Earth leakage current

IEC/EN 61800−5−1

> 3.5 mA AC
> 10 mA DC

Observe regulations and
safety instructions!

Insulation resistance

IEC/EN 61800−5−1

< 2000 m site altitude: overvoltage category III

> 2000 m site altitude: overvoltage category II

Advertising
This manual is related to the following products: