Lenze E94AZMS0314 User Manual

Page 50

Advertising
background image

6

Electrical installation

Important notes

EDK94AZMS DE/EN/FR/ES/IT 8.0

50

l

H1_E_INST−−−−(DUMMYSEITEVOR)−−−

{

Danger!

Hazardous electrical voltage

The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.

Possible consequences:

ƒ

Death or severe injuries when touching the device in the event of an error.

Protective measures:

Implement the measures required in EN 61800−5−1. Especially:

ƒ

Fixed installation
– Implement PE connection in compliance with standards.
– Connect PE conductor twice or PE conductor cross−section

³ 10 mm

2

.

ƒ

Connection with a connector for industrial applications according to
IEC 60309 (CEE):
– PE conductor cross−section

³ 2.5 mm

2

as part of a multi−core supply

cable.

– Provide for suitable strain relief.

(

Stop!

No device protection if the mains voltage is too high

The mains input is not internally fused.

Possible consequences:

ƒ

Destruction of the device if the mains voltage is too high.

Protective measures:

ƒ

Observe the maximally permissible mains voltage.

ƒ

Fuse the device correctly on the supply side against mains fluctuations and
voltage peaks.

Advertising