Rated data, 4technical data – Lenze E94AZMS0314 User Manual

Page 40

Advertising
background image

4

Technical data

Rated data

EDK94AZMS DE/EN/FR/ES/IT 8.0

40

l

H1_Daten−Abmess E94AZMS GG 1−3_en

Rated data

Mains

Voltage

Voltage range

Frequency range

U

Lrated

[V]

U

Lrated

[V]

f [Hz]

3/PE AC

230

180 − 0 % ... 264 + 0 %

45 − 0 % ... 65 + 0 %

3/PE AC

400

320 − 0 % ... 440 + 0 %

45 − 0 % ... 65 + 0 %

3/PE AC

500

400 − 0 % ... 550 + 0 %

45 − 0 % ... 65 + 0 %

Voltage

Freq.

Current [A]

Current [A]

Number

of

phases

[V]

[Hz]



max. +45° C



max. +55° C

E94AZMS0034

230/400/500

50/60

3.2/3.2/3.2

2.0/2.0/2.0

3

E94AZMS0094

230/400/500

50/60

9.0/9.0/9.0

5.6/5.6/5.6

3

E94AZMS0184

230/400/500

50/60

18/18/18

11/11/11

3

E94AZMS0314

230/400/500

50/60

31/31/31

19/19/19

3



Temperature in the control cabinet

Power loss

Inductance

Voltage drop

P

loss

[W]

L [mH]

D

U [V]

E94AZMS0034

15

10

10

E94AZMS0094

23

3.5

10

E94AZMS0184

38

1.1

7.4

E94AZMS0314

48

0.75

7.3

Advertising