ƒ Installation must

– always be in accordance with the operating conditions specified in the Technical

data (

^ 40).

– be carried out to EN 60204−1.

ƒ Please observe the following when selecting the cable type:

– The cables used must comply with the approvals required for the application (e. g.

VDE, UL etc.).

– Fuses and cable cross−sections must be dimensioned in accordance with the

specifications in the documentation for the basic device.

{

Danger!

Dangerous electrical voltage

All power terminals remain live for up to three minutes after mains
disconnection.

Possible consequences:

ƒ

Death or severe injuries when touching the power terminals.

Protective measures:

ƒ

Switch off the power supply and wait for at least three minutes before
working on the power terminals.

ƒ

Make sure that all power terminals are deenergised.

{

Danger!

Dangerous voltage

The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.

Possible consequences:

ƒ

Death or severe injuries when the device is touched in the event of a fault.

Protective measures:

ƒ

Implement the actions required in the EN 61800−5−1. Especially:
– Fixed installation
– PE connection must conform to standards (PE conductor diameter

³ 10 mm

2

or PE conductor must be connected twice)