Residual hazards

2

l

31

EDK94AZRS6 DE/EN/FR/ES/IT 7.0

2.2

Residual hazards

{

Danger!

Dangerous electrical voltage

All power terminals remain live for up to three minutes after mains
disconnection.

Possible consequences:

ƒ

Death or severe injuries when touching the power terminals.

Protective measures:

ƒ

Switch off the power supply and wait for at least three minutes
before working on the power terminals.

ƒ

Make sure that all power terminals are deenergised.

O

Warnings!

Conditions of Acceptability:

ƒ

The products covered by this report are only intended for use
with Power Conversion Equipment (inverters).

ƒ

Consideration shall be given to the field wiring leads. No strain
relief test was performed on the leads.

ƒ

The devices in this report are only evaluated for factory wiring
use.

ƒ

Temperature tests were performed with hook mounted drive.

ƒ

Reactor model E94AZR0544 shall be installed with input wiring
of 4 AWG minimum. Reactor model E94AZR0954 shall be
installed with input wiring of 1/0 AWG minimum.