Electrical installation

Connection data

6

l

46

EDK94AZRS6 DE/EN/FR/ES/IT 7.0

6.3

Connection data

Mains

Terminal X301

Labelling

Description

L1
L2
L3

Connection of the mains phases L1, L2, L3

+

Connection for the supply−side PE conductor with ring cable
lug M8

SSP94FF606

Terminal data

Max. conductor cross−section

Tightening torque

!

[mm

2

]

[AWG]

[Nm]

[lb−in]

E94AZxS0544

50

0

10

88.5

Hexagon

socket 5

E94AZxS0954

95

000

14

124.0

PE connection data

Æ

Starting torque

!

[mm]

[Nm]

[lb−in]

E94AZxS0544

M8

12

106

SW 13

E94AZxS0954

Standard device

Cable X302

Labelling

Description

1
2
3

Filter output conductor (lead with wire end ferrules, colour
BK)

PE

Output−side PE conductor (lead with wire end ferrule,
colour GN/YE)

SSP94FF607

6.4

Mounting steps

Proceed as follows to connect the filter:
1. Connect the filter output cable (X302) to terminal X100 of the standard

device.

2. Connect the mains cable to terminal X301.
3. Attach the supply−side PE conductor to the PE conductor screw using a

ring or fork−type cable lug.

The PE connection must comply with EN 61800−5−1.