Technical data

General data and operating conditions

4

l

35

EDK94AZRS6 DE/EN/FR/ES/IT 7.0

Environmental conditions

Climate

Storage

IEC/EN 60721−3−1

1K3 (−25 ... +60 °C)

Transport

IEC/EN 60721−3−2

2K3 (−25 ... +70 °C)

Operation

IEC/EN 60721−3−3

3K3 (−10 ... +55 °C)
Current derating at +45 ... +55 °C:
Device size 1 ... 7: 2.5 %/°C
Device size 8S ... 10: 1 %/°C

Site altitude

0 ... 4000 m amsl
1000 ... 4000 m amsl: current derating of
5 %/1000 m

Pollution

EN 61800−5−1

Degree of pollution 2

Vibration resistance

(9.81 m/s

2

= 1 g)

Transport

IEC/EN 60721−3−2

2M2

EN 61800−2

2 ... 9 Hz: amplitude 3.5 mm

10 ... 200 Hz: acceleration resistant up to 10 m/s

2

200 ... 500 Hz: acceleration resistant up to 15 m/s

2

Operation

Germanischer
Lloyd

5 ... 13.2 Hz: amplitude ±1 mm
13.2 ... 100 Hz: acceleration resistant up to 0.7 g

IEC/EN 60068−2−6

10 ... 57 Hz: amplitude 0.075 mm

57 ... 150 Hz: acceleration resistant up to 1 g

Mounting conditions

Mounting place

In the control cabinet

Mounting position

Vertical

Free spaces
Dimensions
Weights

^

38