Wiring, 4electrical installation – Lenze EMF2133IB User Manual

Page 48

Advertising
background image

4

Electrical installation

Wiring

EDKMF2133 DE/EN/FR 6.1

48

l

H2_Verdrahtung−TN anzahl

Wiring

ƒ Only use cables which correspond to the listed specifications, see (

^ 48).

ƒ Provide connection to the controllers by means of the bus connector. The bus system

will not be interrupted if the bus connector is removed from the controller.

ƒ Observe the notes and wiring regulations given in the documentation for the control

system.

ƒ Adapt baud rate to the bus cable length.
ƒ Check bus terminating resistors and activate them if necessary.

Specification of the transmission cable

Please follow the specifications of the PROFIBUS user organisation (PUO) for signal cables:

Bus cable specification

Specific resistance

135 − 165

W

/km, (f = 3 − 20 MHz)

Capacitance per unit length

£

30 nF/km

Loop resistance

< 110

W

/km

Core diameter

> 0.64 mm

Core cross−section

> 0.34 mm

2

Cores

Double twisted, insulated and shielded

Terminal data

Electrical connection

Plug connector with screw connection

Possible connections

rigid: 1.5 mm

2

(AWG 16)

flexible:

without wire end ferrule
1.5 mm

2

(AWG 16)

with wire end ferrule, without plastic sleeve
1.5 mm

2

(AWG 16)

with wire end ferrule, with plastic sleeve
1.5 mm

2

(AWG 16)

Tightening torque

0.5 ... 0.6 Nm (4.4 ... 5.3 lb−in)

Bare end

6 mm

Advertising